How Much Creepage Does an Indoor Medium-Voltage Insulator Need?
Short answer. Creepage distance is the specific creepage (mm per kV) multiplied by the highest voltage for equipment, Um. For a 24 kV indoor post insulator, Indisol’s standard range offers between 254 mm and 580 mm of creepage at the same 210 mm height — roughly 10.6 to 24 mm/kV. Which one you need depends on how clean and dry the switchgear stays in service, not on the voltage alone.

Creepage, clearance and height are three different things
- Creepage distance is the shortest path along the surface of the insulator between the two metal fittings. It is what resists surface tracking when the insulator is dirty or wet.
- Clearance is the shortest path through the air. It is what withstands lightning and switching impulses.
- Height mostly sets the clearance. The creepage is set by the profile: the number and depth of the sheds.
That is why an IEC 60273 designation such as JO 4 125 says nothing about creepage: J = indoor post insulator, O = organic material, 4 = 4 kN failing load, 125 = 125 kV lightning impulse withstand. Two insulators with the same designation and the same height can have very different creepage.
How to calculate it
Specific creepage (mm/kV) = creepage distance ÷ Um (phase-to-phase). Example: 501 mm ÷ 24 kV = 20.9 mm/kV.
IEC TS 60815-1 uses the unified specific creepage distance (USCD), referred to the phase-to-earth voltage: USCD = creepage ÷ (Um/√3). The same 501 mm at 24 kV gives 36.2 mm/kV USCD. Always check which of the two a specification means — they differ by a factor of √3.
Reference values
For outdoor insulators, IEC TS 60815-1 links site pollution severity to a reference USCD:
| Site pollution severity | Reference USCD | ≈ specific creepage on Um |
|---|---|---|
| a – very light | 22.0 mm/kV | 12.7 mm/kV |
| b – light | 27.8 mm/kV | 16 mm/kV |
| c – medium | 34.7 mm/kV | 20 mm/kV |
| d – heavy | 43.3 mm/kV | 25 mm/kV |
| e – very heavy | 53.7 mm/kV | 31 mm/kV |
Indoor switchgear usually needs less, because the insulator is sheltered from rain and most pollution. Condensation is the main exception: where the switchgear room is not heated or ventilated, or the panel sees humidity cycles, specify more creepage. Many switchgear manufacturers and utilities set their own minimum — the customer specification overrides any general rule.
What Indisol’s standard range offers
Same voltage, same height, different creepage — taken from our published catalogue:
| Um | Reference | Height | Creepage | mm/kV on Um |
|---|---|---|---|---|
| 12 kV | AE-20 Red S4 (JO 4 75) | 130 mm | 184 mm | 15.3 |
| 12 kV | AE-20 Red S8 (JO 8 75) | 130 mm | 228 mm | 19.0 |
| 12 kV | AEI-10 (JO 8 75) | 130 mm | 385 mm | 32.1 |
| 17.5 kV | AE-17,5/20 S4 (JO 4 95) | 175 mm | 246 mm | 14.1 |
| 17.5 kV | AE-17,5/20 S8 (JO 8 95) | 175 mm | 466 mm | 26.6 |
| 24 kV | AE-20/24 S4 (JO 4 125) | 210 mm | 254 mm | 10.6 |
| 24 kV | AE-20/24 S8 (JO 8 125) | 210 mm | 501 mm | 20.9 |
| 24 kV | AEI-20 | 210 mm | 580 mm | 24.2 |
| 36 kV | AE-30/36 S4 (JO 4 170) | 300 mm | 388 mm | 10.8 |
| 36 kV | AE-30/36 S8 (JO 8 170) | 300 mm | 690 mm | 19.2 |
| 72.5 kV | AER-72,5 | 620 mm | 1 295 mm | 17.9 |
The full table of 44 references, with dimensions, threads and weights, is on the support insulator page.
Choosing
- Clean, dry, heated switchgear room: Series 400 (4 kN) is designed for it.
- Condensation, dust or industrial atmosphere: Series 800, or the AEI series, which adds creepage without adding height — useful when the panel cannot take a taller part.
- Up to 72.5 kV, or a long leakage path: AER series.
- If the customer specification states a minimum, use it: give us the figure and say whether it is on Um or on Um/√3.
Material matters too
Creepage is only half of the answer. The surface must also resist tracking: cast epoxy grades are compared by their comparative tracking index (CTI) and by inclined-plane tracking tests. Hydrophobic cycloaliphatic epoxy is the usual choice where condensation is expected. More on resin families in our epoxy insulator guide.
Common questions
Does a taller insulator always have more creepage?
No. At 210 mm, our 24 kV parts range from 254 mm to 580 mm. The sheds decide.
Can creepage be increased without changing the height?
Yes — with more or deeper sheds, as in the AEI series. The base diameter usually grows.
Is the creepage the same as the “125” in JO 4 125?
No. 125 is the lightning impulse withstand level in kV.
What should I send for a quotation?
Um, the impulse level, the failing load in kN, the maximum height, the creepage (and whether on Um or Um/√3), the threads, and a word on the environment.